8.2.12 AC Input, Motor, Load Sharing or Regen Terminals

1.

Remove the external wiring from the terminals as required.

2.

Remove the retaining nut (17 mm) connecting the terminal bus bar to other bus bar assemblies.

3.

Remove the 2 retaining nuts (13 mm) attaching the terminal bus bar to the terminal block insulation. Slide the terminal bus bar out.

4.

If the terminal block is attached to the input terminal plate (not shown), remove the retaining screw (T40) attaching the terminal block insulation, otherwise
go to step 5.

5.

If the terminal block is not attached to the input terminal plate, remove the retaining nut (13 mm) attaching the terminal block insulation.

Reinstall in reverse order of this procedure. Tighten the 17 mm connecting nuts to 19 Nm (170 in-lbs) and the 13 mm or T40 Torx screw to 9.5 Nm (85 in-lbs).

130BX106.10

1

2

3

Illustration 8.1: Terminal Blocks

1

Retaining nuts (Step 3)

3

Terminal block insulation (Step 4 or 5)

2

Retaining nut (Step 2)

AF-650 GP and AF-600 FP High Power Service Manual