9 ratings tables – GE Industrial Solutions AF-600 FP High Power (460V_575V 150HP and above) User Manual

Page 9

Advertising
background image

1.9 Ratings Tables

DC Voltage Levels

380–480 units

525-600 units and 525–690 units

Inrush Circuit Enabled

370 VDC

548 VDC

Inrush Circuit Disabled

395 VDC

600 VDC

Inverter Undervoltage Disable

402 VDC

553 VDC

Undervoltage Warning

423 VDC

585 VDC

Inverter Undervoltage Re-Enable (warning reset)

442 VDC

602 VDC

Overvoltage Warning (without brake)

817 VDC

1084 VDC

Dynamic Brake Turn On

810 VDC

1099 VDC

Inverter Overvoltage Re-Enable (warning reset)

821 VDC

1099 VDC

Overvoltage Warning (with brake)

828 VDC

1109 VDC

Overvoltage Trip

855 VDC

1130 VDC

Mains supply 3 x 380–480 V
Model number

AF-600 FP

150

200

250

300

350

AF-650 GP

125

150

200

250

300

Light duty current ratings (110%):

Output current

Nominal [A] (380–440 V)

212

260

315

395

480

MAX (60 sec) [A] (380–440 V)

233

286

347

434

528

Nominal [A] (441–480 V)

190

240

302

361

443

MAX (60 sec) [A] (441–480 V)

209

264

332

397

487

Output

Nominal [kVA] (400 V)

147

180

218

274

333

Nominal [kVA] (460 V)

151

191

241

288

353

Typical shaft output

[kW] (400 V)

110

132

160

200

250

[HP]

(460

V)

150

200

250

300

350

Heavy duty torque (160%):
Output current

Nominal [A] (380–440 V)

177

212

260

315

395

MAX (60 sec) [A] (380–440 V)

266

318

390

473

593

Nominal [A] (441–480 V)

160

190

240

302

361

MAX (60 sec) [A] (441–480 V)

240

285

360

453

542

Output

Nominal [kVA] (400 V)

123

147

180

218

274

Nominal [kVA] (460 V)

127

151

191

241

288

Typical shaft output

[kW] (400 V)

90

110

132

160

200

[HP]

(460

V)

125

150

200

250

300

Power loss Light duty [W]

3234

3782

4213

5117

5893

Power loss Heavy duty [W]

2641

2995

3425

3910

4625

Limits and Ranges

Overcurrent Warning

Drive A

RMS

Out

329

394

484

586

735

Overcurrent Alarm (1.5 sec delay)

Drive A

RMS

Out

329

394

484

586

735

Earth (Ground) Fault Alarm

Drive A

RMS

Out

80

95

120

151

180

Short Circuit Alarm

Drive A

RMS

Out

420

502

616

747

936

Heatsink Overtemperature

Degrees C

85

90

105

105

115

Heatsink Undertemperature Warning

Degrees C

0

0

0

0

0

Power Card Ambient Overtemperature

Degrees C

60

60

60

60

60

Power Card Ambient Undertemperature

Degrees C

-20

-20

-20

-20

-20

Mains Phase Warning (5 sec delay)

DC Bus Ripple VAC

50

50

50

50

50

Mains Phase Alarm (25 sec delay)

DC Bus Ripple VAC

50

50

50

50

50

AF-650 GP and AF-600 FP High Power Service Manual