2 control assembly support bracket – GE Industrial Solutions AF-600 FP High Power (460V_575V 150HP and above) User Manual
Page 103
Illustration 7.1: Control Card Access
380–480V: Yellow tape on the main SMPS transformer in the upper right corner.
525–690V: White tape on the main SMPS transformer in the upper right corner.
1
Keypad (Step 2)
8
Power card PCA3
2
Keypad cradle (Step 3)
9
MK102 ring lug connection
3
C-option (if installed)
10
DC bus fuse
4
Mounting screws (Step 5)
11
Control card mounting plate
5
Control assembly support bracket
12
Control card terminal block
6
Attaching hardware
13
Control card (under Keypad)
7
Power card mounting plate
7.2.2 Control Assembly Support Bracket
1.
Remove the control card mounting plate in accordance with procedure.
2.
Remove the 6 mounting nuts (10 mm), see Illustration 7-1.
3.
Remove the control assembly support bracket.
Reinstall in reverse order of this procedure. Tighten the mounting screws to 4 Nm (35 in-lbs).
AF-650 GP and AF-600 FP High Power Service Manual
102
7