GE Industrial Solutions AF-600 FP High Power (460V_575V 150HP and above) User Manual

Page 11

Advertising
background image

Mains supply 3 x 525–690 V

1.

Model number

AF-600 FP

150

200

250

300

350

400

AF-650 GP

125

150

200

250

300

350

400

Light duty current ratings (110%):
Output current

Nominal [A] (525–550 V)

137

162

204

253

303

360

418

MAX (60 sec) [A] (525–550 V)

151

178

224

278

333

396

460

Nominal [A] (551–690 V)

131

155

192

242

290

344

400

MAX (60 sec) [A] (551–690 V)

144

171

211

266

319

378

440

Output

Nominal [kVA] (550 V)

131

154

194

241

289

343

398

Nominal [kVA] (575 V)

130

154

191

241

289

343

398

Nominal [kVA] (690 V)

157

185

229

289

347

411

478

Typical shaft output

[kW] (550 V)

90

110

132

160

200

250

315

[HP] (575 V)

125

150

200

250

300

350

400

[kW] (690 V)

110

132

160

200

250

315

400

Heavy duty torque (160%):
Output current

Nominal [A] (525–550 V)

113

137

162

204

253

303

360

MAX (60 sec) [A] (525–550 V)

170

206

243

306

380

455

540

Nominal [A] (551–690 V)

108

131

155

192

242

290

344

MAX (60 sec) [A] (551–690 V)

162

197

233

288

363

435

516

Output

Nominal [kVA] (550 V)

108

131

154

194

241

289

343

Nominal [kVA] (575 V)

108

130

154

191

241

289

343

Nominal [kVA] (690 V)

129

157

185

229

289

347

411

Typical shaft output

[kW] (550 V)

75

90

110

132

160

200

250

[HP] (575 V)

100

125

150

200

250

300

350

[kW] (690 V)

90

110

132

160

200

250

315

Power loss Light duty [W]

2662

3114

3612

4293

5155

5821

6149

Power loss Heavy duty [W]

2264

2665

2953

3451

4275

4875

5185

Limits and Ranges
Overcurrent Warning

Drive A

RMS

Out

256

256

329

483

483

585

734

Overcurrent Alarm (1.5 sec delay)

Drive A

RMS

Out

256

256

329

483

483

585

734

Earth (Ground) Fault Alarm

Drive A

RMS

Out

54

66

78

96

121

145

172

Short Circuit Alarm

Drive A

RMS

Out

325

325

420

614

614

742

932

Heatsink Overtemperature

Degrees C

85

85

90

110

110

110

110

Heatsink Undertemperature Warning

Degrees C

0

0

0

0

0

0

0

Power Card Ambient Overtemperature Degrees C

60

60

60

60

60

60

60

Power Card Ambient Undertempera-
ture

Degrees C

-20

-20

-20

-20

-20

-20

-20

Mains Phase Warning (5 sec delay)

DC Bus Ripple VAC

70

70

70

70

70

70

70

Mains Phase Alarm (25 sec delay)

DC Bus Ripple VAC

70

70

70

70

70

70

70

1.

AF-600 FP only available up to 600 V

AF-650 GP and AF-600 FP High Power Service Manual

10

1

Advertising