6.1.3 Test Cables

The test cables bypass the main DC bus capacitors and supply DC voltage to the power card from the soft charge card. This provides voltage for testing the power
card without the frequency converter circuitry being powered. The SCR shorting plug ensures that the SCRs do not fire. There are two cable types, the 4x-frame
frequency converters use the 2-pin cable and the 5x-frame frequency converters use the 3-pin cable (see the illustrations below). The 4x-frame cable connects
to the wire harness above the power card by the SMPS fuse to the power card connector MK105. The 5x-frame connects between the soft charge connector MK3
and the power card connector MK105.

130BX64.10

Illustration 6.2: SCR Shorting Plug

Illustration 6.3: Two-Pin 4x-frame Test Cable

Illustration 6.4: Three-Pin 5x-frame Test Cable