7.2.6 Gate Drive Card

1.

Disconnect the cables from the connectors on gate drive card MK100, MK102, MK103, MK104, MK106, and, if the unit has a brake option, MK105, and,
for 380-480 V units with an RFI filter, MK101.

2.

Remove the gate drive card by removing the 6 mounting screws (T25 Torx) from the standoffs.

Reinstall in reverse order of this procedure. Tighten the mounting screws to 2.3 Nm (20 in-lbs).

130BX160.10

2

3

4

5

6

7

1

Illustration 7.1: Gate Drive Card

1

MK100 (temperature sensor)

2

MK101 (RFI filter)

3

MK106

4

MK105 (brake option)

5

MK102 (U)

6

MK103 (V)

7

MK104 (W)