FULLTEST

3

EN - 16

5.1.4. R

PE-2WIRE

MEASUREMENT

Measured quantities and display ranges:
Resistance R

PE

0

 200  (nominal test current 200 mA)

0

 20  (nominal test current 25 A)

Measurement current Im

10

 255 mA (nominal test current 200 mA)

0.2

 30.0 A (

nominal test current 25 A)

1) Select the R

PE-2WIRE

measurement by pressing the FUNC hard key first.

2) Check selected test current (200 mA or 25 A) and modify it if needed by pressing

the Im

NOM

(5)

touch-screen key first.

3) Check selected limit value and modify it if needed by pressing the LIMIT (6) touch-screen key first.

Four independent preset limit values are available in STANDARD limit mode selection for quicker
operations. Select the one closest to wished value and modify it by using the + and touch screen

keys if needed.

4) Check selected mode (MANUAL or TIMER) and modify it if needed by pressing the MODE (7)

touch-screen key first. In MANUAL mode the measurement will start after pressing the
START/STOP button and will stop after pressing the START/STOP button again. In TIMER mode

the measurement will start after pressing the START/STOP button and will stop after elapsing set
measurement time or after pressing the START/STOP button again.

5) Check the status of test lead calibration and carry out the calibration if needed, see the instructions

in chapter “CALIBRATION OF TEST LEADS” above.

6) Select measurement screen by pressing the

(4) touch-screen key and check all settings again.

7) Connect the test leads according to the figure below.

CAUTION

Before connecting test leads to UUT obligatory assure there is no external voltage
higher than 10 V between the test points where test leads will be connected to,

otherwise fuse F4 may blow!

Figure 7

: Connection of test leads in R

PE-2WIRE

function

8) Carry out the measurement by pressing the START/STOP button. Test result will currently be

displayed in green (result lower than or equal to set limit value) or in red colour (result higher than
set limit value). Final result will be equipped with green

symbol and with beep-beep sound

(result OK) or with

red

symbol and with longer beep sound (result not OK) or with yellow

symbol and with beep-beep sound (result OK, but measurement current was too low). See

the

display outlook with test result on figure 5

.

9)

Save the test result by pressing the SAVE hard key twice,

for further instructions see the

“MEMORIZING EXAMPLE” section.