5.5.3. RCD MEASUREMENT

Measured quantities and display ranges:
Trip out time at I

N

/2

0

 1000 ms (AC, A, B, general, selective, delayed)

Trip out time at I

N

0

 1000 ms (AC, A, B, general, selective, delayed)

Trip out time at 2I

N

0

 200 ms (AC, A, general), 0  250 ms (AC, A, selective)

Trip out time at 4I

N

0

 200 ms (B, general), 0  250 ms (B, selective)

Trip out time at 5I

N

0

 50 ms (AC, A, general), 0  150 ms (AC, A, selective)

AUTO test

YES (general, selective)

Trip out current (Ramp test)

10

 110% of I

N

in steps of 5% of I

N

(general)

Input requirements:
Mains voltage U

L/N

(READY condition)

100

 265

V AC

Mains voltage U

L/PE

(READY condition)

100

 265 V AC

1) Select the RCD function by pressing the FUNC hard key first.

2)

Check selected RCD type (AC, A or B) and selected characteristic (GENERAL, SELECTIVE or
DELAYED) and modify it if needed by pressing the TYPE (5) touch-screen key first

. If DELAYED

characteristic is selected, the screen will turn to delay time adjustment mode automatically.

3) Select nominal differential current by pressing the I

N

touch-screen key first.

4) Select wished measurement by pressing the MEAS touch-screen key first (t

/1/2I

N

, t

/I

N

, t

/2I

N

,

t

/5I

N

, I

or AUTO).

5) Check selected polarity and modify it if needed by pressing the POL (8) touch-screen key first.

6) Select measurement screen by pressing the

(4) touch-screen key and check all settings again.

7) Connect the test leads according to one of the figures below.

Figure 20

: Connection of schuko test cable

Figure 21

: Connection of test leads