6.5.5. NOMINAL VOLTAGE menu

This menu shall be used in order to select nominal mains voltage. The voltage may be either 230 or
240 V. It is used in LOOP and U

RES

measurements.

In LOOP measurements it is used for calculation of prospective short-circuit current, see the “LOOP
IMPEDANCE / SHORT-CIRCUIT CURRENT (LOOP)” section.

In U

RES

function (linear mode only) the nominal voltage is used for scaling of measured value, see the

“RESIDUAL VOLTAGE

(U

RES

)

” section.

230 V

240 V

NOMINAL VOL.

Figure 59

: NOMINAL VOL. menu

Select nominal voltage by pressing appropriate touch-screen key, the menu will turn to SETUP menu.

6.5.6. SAFETY menu

In order to set the status of safety input in DIELECTRIC function the SAFETY INPUT menu shall be
used. The safety input may be enabled or disabled.

Safety input disabled: DIELECTRIC test is active regardless of the safety input condition (safety switch
may be closed or opened or not connected at all).

Safety input enabled: DIELECTRIC test is active only if safety input condition is sufficient (safety switch
must be closed).

This safety input status does not influence to any other function except DIELECTRIC.

DISABLED

ENABLED

SAFETY INPUT

Figure 60

: SAFETY INPUT menu

Select the safety status by pressing appropriate touch-screen key, the menu will turn to SETUP menu.