Technical specifications – HT instruments FULLTEST3 User Manual

Page 79

Advertising
background image

FULLTEST

3

EN - 78

14. TECHNICAL SPECIFICATIONS

14.1.

MEASUREMENT FUNCTIONS

CONTINUITY OF PROTECTIVE CONDUCTOR (R

PE-2WIRE, 0.2A

)

Display range

(

)

Resolution

(M

)

Accuracy

Overvoltage protection

0.00

 19.99

0.01

± (3% rdg. + 3 dgt)

CAT III 300 V

20.0

 200.0

0.1

Standard test leads:

2 × 2 m, 2.5 mm

2

Open-circuit test voltage:

Approx. 4.5 V AC (floating)

Short-circuit test current:

< 0.6 A (standard test leads)

Test current:

> 0.2 A (standard test leads and external resistance < 20

)

Display range of test current:

10

 255 mA

Accuracy of displayed test current:

± (3% rdg. + 2 dgt)

Limit value:

Adjustable 0.01

 19.99, 20.0  200.0 

Measurement principle:

Two-wire connection

Test lead calibration:

Up to 5.00

Protection against ext. voltage:

Fuse F4 (T20A/500V, 6.3×32 mm), blown fuse automatically

detected in R

PE

measurement

Detection of external voltage

Yes

-

U

EXT

lim = 3 V AC (between two R

PE

or between two

SENSE terminals before measurement)

-

U

EXT

lim = 10 V AC (between two R

PE

or between two

SENSE terminals during measurement)

-

U

EXT

lim = 30 V AC approx. (between any R

PE

/SENSE

terminal and GND before/during measurement)

CONTINUITY OF PROTECTIVE CONDUCTOR (R

PE-2WIRE, 25A

)

Display range

(

)

Resolution

(M

)

Accuracy

Overvoltage protection

0.000

 1.999

0.001

± (3% rdg. + 3 dgt)

CAT III 300 V

2.00

 20.00

0.01

Standard test leads:

2 × 2 m, 2.5 mm

2

Open-circuit test voltage:

Approx. 4.5 V AC (floating)

Short-circuit test current:

< 30 A (standard test leads)

Test current (25A range):

> 25 A (standard test leads and external resistance < 0.1

)

> 10 A (standard test leads and external resistance < 0.5

)

Display range of test current:

0.2

 30.0 A

Accuracy of displayed test current:

± (3% rdg. + 1 dgt)

Limit value:

Adjustable 0.01

 20.00  or

Calculation through loop impedance or

Calculation through wire length

Measurement principle:

Two-wire connection

Test lead calibration:

Up to 5.00

Protection against ext. voltage between
current terminals (R

PE

):

Fuse F4 (T20A/500V, 6.3×32 mm), blown fuse automatically

detected

Detection of external voltage

Yes, see the limit values explanation above (

PROTECTIVE

CONDUCTOR (R

PE-2WIRE, 0.2A

))