HT instruments FULLTEST3 User Manual

Page 29

Advertising
background image

FULLTEST

3

EN - 28

Figure 16

: Connection of test leads

8) Carry out the test by pressing the START/STOP button. Warning with explanation of how to

connect test leads with regard to selected test voltage will be displayed. Check the connection then
confirm it by pressing the YES touch-screen key, the message “READY” will appear and will stay

present for 10 seconds. START/STOP button is active while “READY” message is present. Press
and keep pressing the START/STOP button, test voltage will be applied to test terminals. The test

will be stopped after releasing the START/STOP button (MANUAL or BURN mode) or after
elapsing set test time (RAMP mode).

Test result will currently be displayed in green colour if it is lower than or equal to set limit value.
Final result will be equipped with green

symbol and with beep-beep sound (result OK). If break

through occurred during the test then the test will be stopped and limit test current will be displayed
in red

colour equipped with red

symbol and with longer beep sound

. See the display outlook

with test result on the

figure 13.

9)

Save test result by pressing the SAVE hard button twice,

for further instructions see the

“MEMORIZING EXAMPLE” section.

SAFETY INPUT
In order to reach higher level of safety the SAFETY INPUT connector is installed. Safety switch of a

mechanical barrier can be connected there in order to disable DIELECTRIC function in case the safety
switch is opened. For this purpose select SAFETY INPUT enabled mode in the menu as follows:
MENU hard key

SETUP touch-screen key  SAFETY touch-screen key  ENABLED touch-

screen key.

WARNING LAMP
According to EN 50191 the highest level of safety must be undertaken when working with high voltages

like used in DIELECTRIC test. For this purpose the FULLTEST 3 offers an output to drive the high
voltage warning lamp. Use only the lamps supplied by original supplier of the FULLTEST 3 tester.

CAUTION

Always connect COM terminal to GND if measured UUT is grounded,

otherwise possible capacitive leakage current may flow to ground which may

disturb the measurement!

Measurement time in MANUAL mode is limited to 60 min!

The following specific information can be shown on the display during measurement:

Information displayed

Description

EROR1!

Internal fuse may be blown!
The fuse is not customer replaceable, send the tester into

a service department.