5.12.2. LEAKAGE CURRENT MEASUREMENT USING CURRENT CLAMP

Measured quantities and display ranges:
Leakage current I

LEAK

measured by clamp

0

 1000 mA (1000 mA range)

0

 100 A (100 A range)

0

 1000 A (1000 A range)

1) Select I

LEAK

function by pressing the FUNC hard key first.

2) Select CLAMP mode by pressing the MODE touch-screen key first.

3) Check selected measurement range and modify it if needed by pressing the RANGE (4) touch-

screen key first.

4) Check selected limit leakage current by pressing the LIMIT (5) touch-screen key first. Four

independent limit values are available for quicker operations. Select the closest one and modify it

by using the + and touch screen keys if needed.

5) Select measurement screen by pressing the

touch-screen key and check all settings again.

6) Connect the current clamp to measured wiring according to the figure below.

IPE

Load

Figure 44

: Connection of current clamp in I

LEAK

measurement, CLAMP mode

7) Start the measurement by pressing the START/STOP button. The measurement will start to run

and will be stopped after pressing the START/STOP button again. Measurement result will be

currently displayed in green colour

if it is lower than or equal to set limit value

or in red colour if it is

higher than set limit value. Final result will be equipped with green

symbol and with beep-beep

sound if it is OK or wit

h red

symbol and with longer beep sound if it is not OK

. See the display

outlook with test result on the

figure 42

.

8)

Save the test result by pressing the SAVE hard key twice,

for further instructions see the

“MEMORIZING EXAMPLE” section.