5.5. RCD (RCD)

5.5.1. RCD DISPLAY EXPLANATION

Adjustable/selectable parameters:
TYPE - type of RCD

AC, A or B

CHARACTERISTIC - RCD characteristic

GENERAL, SELECTIVE or DELAYED

I

N

- nominal differential current

10, 30, 100, 300, 500, 650 or 1000 mA

MEAS - type of measurement

t

/1/2I

N

, t

/I

N

, t

/2I

N

, t

/5I

N

, I

or AUTO

POL - test current polarity

POS (positive) or NEG (negative)

DELAY – delay time in DELAY characteristic

0

 700 ms

Figure 17

: Display with RCD test result

1 ..... Selected function.
2 ..... Selected limit contact voltage (25 or 50 V). It can be selected in MENU

SETUPCONTACT

VOL. menu.

3 ..... Sub-results - mains voltages U

L/N

and U

L/PE

at which the test was carried out.

4 ..... Measurement screen touch-screen key.

5 ..... TYPE touch-screen key to select the type of RCD (AC, A or B) and characteristic (GENERAL,

SELECTIVE or DELAYED). Currently selected type and characteristic are displayed on the bottom

of the key.

6 ..... I

N

touch-screen key to select nominal differential current of the RCD (10, 30, 100, 300, 500, 650

or 1000 mA). Currently selected value is displayed on the bottom of the key.

7 ..... MEAS touch-screen key to select the measurement (t

/1/2I

N

, t

/I

N

, t

/2I

N

, t

/5I

N

, I

or AUTO

).

Currently selected measurement is displayed on the bottom of the key.

8 ..... POL touch-screen key to select test current polarity (POS - positive or NEG - negative).

9 ..... Test result (in green colour - result OK, in red colour - result not OK).
10 ... Real time clock (hh.mm.ss).

11 ... Unit of the test result (ms).
12 ... Measurement result status (symbol

in green colour - result OK, symbol

in red colour - result

not OK).