FULLTEST

3

EN - 33

5.6. LOOP IMPEDANCE / SHORT-CIRCUIT CURRENT (LOOP)

• According to EN 60204-1, the conditions for protection against electric shock in installations with

automatic disconnection of mains voltage are:

• Measurement or evaluation of fault loop impedance and testing the over-current protection device

involved in the fault loop.

• Limit values are shown in the Table 10 of EN 60204-1.

5.6.1. LOOP DISPLAY EXPLANATION

Adjustable/selectable parameters:
MODE - measurement mode

LOOP

L/N

, LOOP

L/L

, LOOP

L/PE

, IMP57

L/N

, IMP57

L/L

or IMP57

L/PE

LIMIT - limit value mode

STD, kA, I

2

t, TRIP CURR. or Ut, see the explanation below

Ib – breaking capacity of protection 1, 1.5, 3, 4.5, 6, 10, 15, 16, 20 or 25 kA

PROTECTION - type of protection MCB B, MCB C, MCB D, MCB K, FUSE gG or FUSE aM
In - nominal current of protection

See the values in chapter “LIMIT VALUE EXPLANATION” below

Tset

-

max allowed tripping time

0.1 s, 0.2 s, 0.4 s or 5 s

WIRE - wire material

Cu (Copper) or Al (Aluminium)

COATING - wire coating

PVC, BUTYL RUBBER or EPR/XLPE

SECTION - wire section

1, 1.5, 2.5, 4, 6, 10, 16, 25, 35, 50 or 70 mm

2

N - number of conductors

1

 99

Figure 22

: Display with LOOP

L/N

test result

1 ..... Selected function.
2 ..... Selected nominal voltage (230 or 240 V) needed for calculation of short-circuit current.

3 ..... READY message. It is displayed when present mains voltage U

L/L

, U

L/N

or

U

L/PE

within required

range is present.

4 ..... Sub-results - mains voltage U

L/PE

or

U

L/PE

or

U

L/L

at which the measurement has been done and

calculated prospective short-circuit current I

SC

.

5 ..... Measurement screen touch-screen key.
6 ..... MODE touch-screen key to select measurement mode (LOOP L/N, LOOP L/L, LOOP L/PE, IMP57

L/N, IMP57 L/L or IMP57 L/PE). Currently selected mode is displayed on the bottom of the key.

7 ..... LIMIT touch-screen key to select limit mode (STD, kA, I

2

t, TRIP CURR. or Ut). Currently selected

mode is displayed on the bottom of the key.

8 ..... PROT. (protection) touch-screen key to select the type of protection (MCB B, MCB C, MCB D,

MCB K, FUSE gG or FUSE aM) and nominal current of selected protection. Currently selected type
is displayed on the bottom of the key.