HT instruments FULLTEST3 User Manual

Page 53

Advertising
background image

FULLTEST

3

EN - 52

5.10.2. PHASE SEQUENCE MEASUREMENT

Measured quantities and display ranges:
Phase sequence

1.2.3. or 2.1.3.

Phase-to-phase voltage U

L1/2

360

 460 V

Phase-to-phase voltage U

L2/3

360

 460 V

Phase-to-phase voltage U

L3/1

360

 460 V


1) Select the PHASE

SEQ

function by pressing the FUNC hard key first.

2) Connect the test leads to tested socket/wiring according to the figure below.

Figure 39

: Connection of test leads in PHASE SEQUENCE measurement

3) Carry out the measurement by pressing the START button. The measurement will be done and

test result will be displayed in green colour equipped

and with beep-beep sound if it is in

accordance with referential direction

(1.2.3.)

. If the result is not in accordance with referential

direction (

2.1.3.)

then it will be displayed

in red colour equipped

and with longer beep sound

. See

the display outlook with test result on the

figure 38.

4)

Save the test result by pressing the SAVE hard key twice,

for further instructions see the

“MEMORIZING EXAMPLE” section.

5)

Press the EXIT hard key to clear displayed result, actual input voltages U

L1/2

, U

L2/3

, U

L3/1

will start

to be displayed again.

The following specific information can be shown on the display during the measurement:

Information displayed

Description

VOLTAGE OUT OF RANGE

One or more phase-phase voltages are out of required
range (360

 460 V).

1.1.X

At least one of measured phases was disconnected during
the measurement.

Connect all three phases and repeat the measurement.