3

EN - 35

-

2, 4, 6, 8, 10, 12, 16, 20, 25, 32, 40, 50, 63, 80, 100, 125, 160,

200, 250, 315, 400, 500, 630, 800, 1000 or 1250 A (FUSE gG)

- 2, 4, 6, 8, 10, 12, 16, 20, 25, 32, 40, 50, 63, 80, 100, 125, 160,

200, 250, 315, 400, 500 or 630 A (FUSE aM)

- Tset (max trip time)

0.1, 0.2, 0.4 or 5 s

Ut - verification if short-circuit current is high enough over-current protection device to react within set

time.

On bases of entered over-current protection device (PROTECTION), nominal current of the over-current

protection device (In) and Tset required short-circuit current (Ia) is calculated. Measured I

SC MIN

must

be higher than or equal to calculated current Ia. Entered parameters can be selected among the

following values:
- PROT (type of protection)

MCB B, MCB C, MCB D, MCB K, FUSE gG or FUSE aM

- In (nominal current)

- 6, 10, 13, 16, 20, 25, 32, 40, 50 or 63 A (MCB B)

- 0.5, 1, 1.6, 2, 4, 6, 10, 13, 16, 20, 25, 32, 40, 50 or 63 A (MCB C)

- 0.5, 1, 1.6, 2, 4, 6, 10, 13, 16, 20, 25 or 32 A (MCB D, MCB K)

-

2, 4, 6, 8, 10, 12, 16, 20, 25, 32, 40, 50, 63, 80, 100, 125, 160,

200, 250, 315, 400, 500, 630, 800, 1000 or 1250 A (FUSE gG)

- 2, 4, 6, 8, 10, 12, 16, 20, 25, 32, 40, 50, 63, 80, 100, 125, 160,

200, 250, 315, 400, 500 or 630 A (FUSE aM)

- Tset (max trip time)

0.1, 0.2, 0.4, 5 or 10 s


5.6.3. PROSPECTIVE SHORT-CIRCUIT CURRENT CALCULATION

Evaluation table and short-circuit current calculation:

LIMIT mode TT – Evaluation condition

TN – Evaluation condition

L/L

STD

No evaluation

No evaluation

kA I

SC L/L MAX 3PH

< BC

I

SC L/L MAX 3PH

< BC

I

2

t (I

SC L/L MAX 3PH

)

2

× t

< (K × N × S)

2

(I

SC L/L MAX 3PH

)

2

× t

< (K × N × S)

2

TRIP CURR.

I

SC L/L MIN 2PH

Tmax, Tmax < Tlim

I

SC MIN 2PH

Trip time T, T < Tlim

Ut

L/N

STD

No evaluation

No evaluation

kA

ISC L/L MAX 3PH < BC

ISC L/L MAX 3PH < BC

I

2

t

(ISC L/N MAX)

2

× t

< (K × N × S)

2

(ISC L/N MAX)

2

× t

< (K × N × S)

2

TRIP CURR.

ISC MIN 2PH

 Trip time T, T < Tlim

ISC MIN 2PH

 Trip time T, T < Tlim

Ut

L/N

STD

No evaluation

No evaluation

kA

ISC MAX L/N < Breaking capacity
IB

ISC MAX L/N < Breaking capacity IB

I

2

t

(ISC MAX L/N)

2

× T

< (K × N × S)

2

(ISC MAX L/N)

2

× T

< (K × N × S)

2

TRIP CURR.

ISC MIN L/N

 Trip time T, T <

Tlim

ISC MIN L/N

 Trip time T, T < Tlim

L/PE

STD

No evaluation

No evaluation

kA

ISC MAX L/PE < Breaking capacity
IB

ISC MAX L/PE < Breaking capacity IB

I

2

t

(ISC MAX L/PE)

2

× T

< (K × N × S)

2

(ISC MAX L/PE)

2

× T

< (K × N × S)

2

TRIP CURR.

ISC MIN L/PE

 Trip time T, T <

Tlim

ISC MIN L/PE

 Trip time T, T <

Tlim

Ut

ISC MIN L/PE > N × In

ISC MIN L/PE > N × In