9 ..... WIRE touch-screen key to select the material of measured wire (Cu or Al), coating (PVC, BUTYL

RUBBER or EPR/XLPE), section (1, 1.5, 2.5, 4, 6, 10, 16, 25, 35, 50 or 70 mm

2

) and number of

conductors (1

 99). Currently selected material is displayed on the bottom of the key.

10 ... Measurement result (in green colour - result OK, in red colour - result not OK).
11 ... Real time clock (hh.mm.ss).
12 ... Unit of the test result (

).

13 ... Measurement result status (symbol

in green colour - result OK, symbol

in red colour - result

not OK).

5.6.2. LIMIT VALUE EXPLANATION

There are five possibilities to select the limit prospective short-circuit current I

SC LIM

, which is the bases

for final evaluation.

STD - no verification.

No limit is used in this case meaning test result is not evaluated and is therefore always considered as
neutral (displayed in white colour)

.

kA - verification if short-circuit current is lover than breaking capacity of involved over-current protection
device.

Measured I

SC MAX

must be lower or equal than entered breaking capacity Ib of involved over-current

protection device, where breaking capacity Ib can be selected among the following values:
- Ib (breaking capacity)

1, 1.5, 3, 4.5, 6, 10, 15, 16, 20 or 25 kA

I

2

t - verification if over-current protection device reacts before wires are overheated and thus damaged.

On bases of measured I

SC MAX

and entered over-current protection device (PROTECTION) and

nominal current of the over-current protection device (In) trip out time of the over-current protection

device (t) is calculated. See the evaluation equation in the table “PROSPECTIVE SHORT-CIRCUIT
CURRENT CALCULATION” below. Entered parameters can be selected among the following values:
- PROT (type of protection)

MCB B, MCB C, MCB D, MCB K, FUSE gG or FUSE aM

- In (nominal current)

- 6, 10, 13, 16, 20, 25, 32, 40, 50 or 63 A (MCB B)

- 0.5, 1, 1.6, 2, 4, 6, 10, 13, 16, 20, 25, 32, 40, 50 or 63 A (MCB C)

- 0.5, 1, 1.6, 2, 4, 6, 10, 13, 16, 20, 25 or 32 A (MCB D, MCB K)

-

2, 4, 6, 8, 10, 12, 16, 20, 25, 32, 40, 50, 63, 80, 100, 125, 160,

200, 250, 315, 400, 500, 630, 800, 1000 or 1250 A (FUSE gG)

- 2, 4, 6, 8, 10, 12, 16, 20, 25, 32, 40, 50, 63, 80, 100, 125, 160,

200, 250, 315, 400, 500 or 630 A (FUSE aM)

- MATERIAL (wire material)

Cu (Cupper) or Al (Aluminium)

- COATING (wire coating)

PVC, BUTYL RUBBER or EPR/XLPE

- SECTION (wire section)

1, 1.5, 2.5, 4, 6, 10, 16, 25, 35, 50, 70 mm

2

- N (number of conductors)

1

 99

TRIP CURRENT - verification if over-current protection device reacts within set time at measured short-

circuit current.
On bases of measured I

SC MIN

and entered over-current protection device (PROTECTION) and nominal

current of the over-current protection device (In) trip out time is calculated which must be lower than or
equal to entered Tset. Entered parameters can be selected among the following values:
- PROT (type of protection)

MCB B, MCB C, MCB D, MCB K, FUSE gG or FUSE aM

- In (nominal current)

- 6, 10, 13, 16, 20, 25, 32, 40, 50 or 63 A (MCB B)

- 0.5, 1, 1.6, 2, 4, 6, 10, 13, 16, 20, 25, 32, 40, 50 or 63 A (MCB C)

- 0.5, 1, 1.6, 2, 4, 6, 10, 13, 16, 20, 25 or 32 A (MCB D, MCB K)