5.8. RESIDUAL VOLTAGE (URES)

What are residual voltages? Residual voltages are the voltages that remain present even after
switching off a machine or device. This can be caused e.g. by built in capacitors or subsequent

generators. This measurement is performed by using the U

RES

function.

• According to

EN 60204-1, accessible live parts connected to dangerous voltage must discharge

within 5 seconds (permanently connected machines) or within 1 second (plugged-in machines) down
to 60 V. Proof of this must be given through tests.

In the event of non-compliance, additional measures (discharge devices, warning information, covers
etc.) according to EN 60204-1 must be taken.

• With FULLTEST 3 tester the residual voltage can be measured 1 s or 5 s after switching off tested

machine. Measurement of residual

voltage can be carried out in linear or non-linear mode, see the

section "EXPLANATION OF LINEAR MODE" or section "EXPLANATION OF NONLINEAR MODE".

5.8.1. EXPLANATION OF LINEAR MODE

In linear mode it is assumed there are only

"

linear

"

components involved in discharging process

(capacitors, resistors, inductors etc.) and therefore discharge characteristic is exponential, see the

diagram below.

In linear mode displayed result is scaled to peak value of input voltage in order to evaluate most critical
situation, see the figure below.

U

(measured)

RES

t

1s / 5s

1s / 5s

U

U

(correct value)

RES

Coincidential switch off

at any mains voltage

Figure 30

: Discharge diagram in linear circumstances

For scaling of measured U

RES

voltage Un of mains installation is needed, so it must be selected in prior

to the measurements.


How to select the nominal voltage Un:
Press the MENU

SETUPNOMINAL VOL. touch-screen keys and select 230 V or 240 V. S

ee the

chapter “6.5.4. NOMINAL VOLTAGE menu”.

In linear mode the FULLTEST 3 detects automatically two standard system voltages:

a) Selected nominal voltage Un = 230 V
230 V ............................ U

IN

= 230 V

 10%

400 V ............................ U

IN

= 400 V

 10%


b) Selected nominal voltage Un = 240 V:
240 V ............................ U

IN

= 240 V

 10%

415 V ............................ U

IN

= 415 V

 10%