HT instruments FULLTEST3 User Manual

Page 83

Advertising
background image

FULLTEST

3

EN - 82

RCD test (RCD)

RCD types / characteristics:

AC, A or B / General, Selective or Delayed

Measurement modes:

x1/2I

N

, x1I

N

, x2I

N

, xKI

N

(K = 4 B type, K=5 AC, A type),

I

(RAMP), AUTO (sequence: x1/2, x1, xK)

Nominal currents:

10, 30, 100, 300, 500, 650 or 1000 mA

Accuracy of test currents (10 mA):

- 10% / + 0% (I

N

/2)

+ 10% / - 0% (I

N

, 2I

N

, KI

N

)

Accuracy of test currents (30

1000 mA): - 5% / + 0% (I

N

/2)

+ 5% / - 0% (I

N

, 2I

N

, KI

N

)

Input voltage range / frequency:

100

 265 V / (50 / 60 Hz) ± 0.5 Hz

Contact voltage limits:

25 V or 50 V selectable

Test current polarity:

POSITIVE or NEGATIVE selectable

Test duration (ms) – TT/TN system:

I

N

(mA)

Ч1/2

Ч1

Ч2

ЧK

AUTO

RAMP

G, S, D

G, S, D

G

S

D

G

S

D

G

S

D

G

S

D

10
30

100

AC 1000

1000 200 250 50 150

320

A 1000

1000 200 250 50 150

320

B 1000

1000

200 250

320

300

AC 1000

1000 200 250 50 150

320

A 1000

1000 200 250 50 150

320

B 1000 1000

320

500

AC 1000

1000 200 250 50 150

320

A 1000

1000 200 250 320

B 1000 1000

320

650

AC 1000

1000 200 250 50 150

320

A 1000

1000 200 250 320

B

1000

AC 1000

1000 200 250 320

A 1000 1000
B

Resolution: 1ms, Accuracy:

± (3% rdg + 2 ms)

Mains voltage

U

L/N

,

U

L/PE

:

Display range

(V)

Resolution

(V)

Accuracy

100

 265

1 ±

(3%

rdg.)

Input resistance (U

L/N,

U

L/PE

): 450

k


Ramp test:

YES, current range 10

 110% of I

N

in steps of 5% of I

N

AUTO TEST:

YES, test steps are as follows:

- t/I

N

/2 (pos. polarity)

- t/I

N

/2 (neg. polarity)

- t/I

N

(pos. polarity)

- t/I

N

(neg. polarity)

- t/5I

N

, (pos. polarity)

- t/5I

N (neg. polarity)

Advertising