6.1.2 Fast Sample Rate

If automatic density correction is disabled, this register returns the level sensor fast sample rate
as shown. If automatic density correction is enabled, this register shall return the sum of the
level sensor and conductivity sensor fast sample rates.

6.2 Parameter Registers—Level

Register

Size

(registers)

Mode & Access Level

(R/W)

Data

Type

Description

Pressure

1038

2

R1

float

Measured value, P

m

1040

1

R1

ushort Parameter ID = 2 (pressure)

1041

1

R1/W2

ushort Units ID

17 = PSI (default)

19 = KPa

20 = bar

21 = mbar

22 = mmHg

1042

1

R1

ushort Data Quality ID

1043

2

R1/W3

float

Off line sentinel value

(default = 0.0)

1045

1

R1

16 bits Available Units = 0x003D (61)

Temperature

1046

2

R1

float

Measured value

1048

1

R1

ushort Parameter ID = 1 (temperature)

1049

1

R1/W2

ushort Units ID

1 =

°C (default)

2 =

°F

1050

1

R1

ushort Data Quality ID

1051

2

R1/W3

float

Off line sentinel value (default = 0.0)

1053

1

R1

16 bits Available Units = 0x0003 (3)

45