8.16 Communication Control Registers

8.17 Sensor Connection Registers

Register

XXXX

Size

(registers

Mode

(R/W)

Data

Type

Description

9300

1

R1

ushort Max Sensor Connections (1-32)

9301-302

2

R1

32 bits Sensor Connection Status

Sensor Map Registers

RDO Sensor

9303

1

R1

ushort Connection 1 sensor id

9304

1

R1

16 bits Connection 1 sensor status

9305

1

R1/W2

ushort Connection 1 sensor command

9306

1

R1

ushort Connection 1 sensor data register map version

9307

1

R1

ushort Connection 1 sensor data register offset

Conductivity Sensor

9308

1

R1

ushort Connection 2 sensor id

9309

1

R1

ushort Connection 2 sensor status

9310

1

R1

ushort Connection 2 sensor command

Register

XXXX

Size

(registers

Mode

(R/W)

Data

Type

Description

9200

1

R/W

ushort

Device Address (1-247, default = 1)

9201

1

R/W

ushort

Serial Communication Configuration

9202

1

R/W

ushort

EOM timeout (1000-15000 ms, default = 1000)

9203

1

R/W

ushort

EOS timeout (5000-60000 ms, default = 5000)

9204

1

R

ushort

Max allowed baud rate id (0-7)

9205

1

R

ushort

Max Message/Response size (bytes)

9206-207

2

R/W

ulong

Good message counter

9208

1

R/W

ushort

Bad message counter

9209

1

R/W

ushort

Exception response counter

70