8.37 Sensor Map Registers

8.37.1

Sensor ID Registers

These registers duplicate the Sensor ID register provided in each sensor’s Sensor Data Header
Register block. If a sensor connection is open, the probe returns a zero. If an attempt is made to
access a Sensor ID register that is not mapped to a sensor (one that exceeds the maximum
number of sensors supported by the probe), the probe will return an exception response with
error code 0x02 (illegal data address).

8.37.2

Sensor Status Register

These registers duplicate the sensor status register provided in each sensor’s Sensor Data
Header Block. If a sensor connection is open, the probe returns a zero. If an attempt is made to
access a sensor status register that is not mapped to a sensor (one that exceeds the maximum
number of sensors supported by the probe), the probe will return an exception response with
error code 0x02 (illegal data address).

8.37.3

Sensor Command Register

These registers are used to send commands to a sensor. The behavior of the sensor command
register and the commands available is different from SIS-1&2 and SIS-3. The sensor command
register is primarily used to calibrate the sensor. Failure of the command is returned in the
response exception.

If an attempt is made to access a sensor command register that is not mapped to a sensor (one
that exceeds the maximum number of sensors supported by the probe), the probe will return an
exception response with error code 0x02 (illegal data address).

ID

Name

Description

0xE000

Calibration Mode On

Put sensor in the calibration mode.

0xE001

Calibration Update

Commit new calibration to memory.

0xE002

Calibration Mode Off

Put sensor in the normal operating mode.

0xE003

Restore Cal Defaults

Restore factory default calibration for sensor only.

0xE004

Restore sensor defaults

Restore factory defaults for calibration, parameters and

units, sentinel values, etc. for sensor only.

8.37.4

Sensor Data Register Map Version Registers

These registers specify the version of the sensor data register map pointed to by the Sensor
Data Register Offset registers. If a sensor connection is open, the probe shall return a zero. If
an attempt is made to access a sensor map version register that is not mapped to a sensor (one
that exceeds the maximum number of sensors supported by the probe), the probe will return an
exception response with error code 0x02 (illegal data address).