4 mask write register, Mask write register – In-Situ Aqua TROLL 400 Modbus and SDI-12 Reference Guide User Manual

Page 61

Advertising
background image

Where Byte Count is the #bytes in the Data Payload (does not include CRC bytes).

Byte Count = 2*Register Count.

The register count is limited to a single data format field. If an attempt is made to write a data
field with an incorrect register count, the device will return a Modbus exception response with
error code 0x80.

8.10.4

Mask Write Register

This command will set and/or clear one or more bits in a single register.

Message :

Response:

Address

1 Byte

1-247

Address

1 Byte

1-247

Function Code

1 Byte

0x16

Function Code

1 Byte

0x16

Data Address

2 Bytes

0 to 0xFFFF Data Address

2 Bytes

0 to 0xFFFF

And_Mask

2 Bytes

0 to 0xFFFF And_Mask

2 Bytes

0 to 0xFFFF

Or_Mask

2 Bytes

0 to 0xFFFF Or_Mask

2 Bytes

0 to 0xFFFF

CRC

2 Bytes

CRC

2 Bytes

Register = (Register Value AND And_Mask) OR (Or_Mask AND (NOT And_Mask))

And_Mask: 0 = bits to change, 1 = bits to leave unchanged.

Or_Mask: 0 = bits to clear, 1 = bits to set.

Example: - set bit 1 (LSB), clear bit 2, leave remaining bits unchanged

Old Value:

0x007E

0000 0000 0111 1110

And_Mask:

0xFFFC

1111 1111 1111 1100

Or_Mask:

0x0001

0000 0000 0000 0001

New Value:

0x007D

0000 0000 0111 1101

This command is useful in a bit mapped register where the Master wants to set some bits of a
register that are mapped to a feature without disturbing the other bits of the register that might
be mapped to a different feature.