11 instrument manufacturer data types, 1 short, 2 unsigned short – In-Situ Aqua TROLL 400 Modbus and SDI-12 Reference Guide User Manual

Page 63: 3 long, Instrument manufacturer data types, Short, Unsigned short, Long

Advertising
background image

Byte Offset

Field Description

Type

Value

18-21

Device Serial Number

ulong

22-23

Max Message/Response Size

(bytes)

ushort

24-25

Max Baud Rate ID

ushort

26-27

CRC

The specific field values such as device ID, baud ID, etc. are documented in the sections that
follow.

8.11 Instrument Manufacturer Data Types

Modbus defines all I/O in terms of 2 byte blocks called registers. Modbus does not formally
define blocks for floating point values or strings. In the manufacturer’s implementation, these
fundamental types and others are handled by combining two or more registers. The
manufacturer data type implementations are defined in the following sections.

8.11.1

Short

A 2-byte signed integer contained in a single register data address. IEEE standard.

Where S = sign bit

8.11.2

Unsigned Short

A 2-byte unsigned integer contained in a single register data address. IEEE standard.

8.11.3

Long

A 4-byte signed integer contained in two register data address’s. IEEE standard.

Where S = sign bit

Byte 2

Byte 3

Byte 1

Byte 0

SXXX

XXXX

XXXX XXXX

MSB

LSB

XXXX XXXX

XXXX XXXX

Byte 1

Byte 0

XXXX

XXXX

XXXX XXXX

MSB

LSB

Byte 1

Byte 0

SXXX

XXXX

XXXX XXXX

MSB

LSB

63