2.3 I/O Module Specification

Data format

(1) Basic registers

Change detection status and Input data

S2T

S2

Description

XWn

%IWn

Rising edge detection status

XWn+1

%IWn+1

Falling edge detection status

XWn+2

%IWn+2

Input data

XWn+3

%IWn+3

No use (reserved)

[Rising edge detection status bit assignment;

Bit

F

E

D

C

B

A

9

8

7

6

5

4

3

2

1

0

US

US

US

US

US

US

US

US

US

US

US

US

US

US

US

US

US: When corresponding bit of input data changes from OFF to ON, it sets to ’1

[Falling edge detection status bit assignment]

Bit

LS: When corresponding bit of input data changes from ON to OFF, it sets to ’1

[Input data bit assignment]]

Bit

F

E

D

C

B

A

9

8

7

6

5

4

3

2

1

0

LS

LS

LS

LS

LS

LS

LS

LS

LS

LS

LS

LS

LS

LS

LS

LS

F

E

D

C

B

A

9

8

7

6

5

4

3

2

1

0

F

E

D

C

B

A

9

8

7

6

5

4

3

2

1

0

This register reflects the current input signal status.

When the interrupt enable flag is set to ON (DE=’T) and the rising edge detection is selected

(UE=’T), the CD633 sets corresponding bit of the change detection status register (US) and

generates interrupt to the controller at the time of input signal change from OFF to ON.

As same manner, when the falling edge detection is selected (LE=’T), the CD633 generates

interrupt at the time of input signal change from ON to OFF.

If both UE and LE are set’T, the interrupt is generated at the time of both change from OFF

to ON and from ON to OF

The change detection status is cleared to ’O’, when the controller is read the change

detection status and input data. Therefore make the application program to read the change

detection status and input data (3 words) at the same time by the direct I/O instruction, in the