Function, Expression, Execution condition – Toshiba SX 2000 User Manual

Page 62: Operand, Exampie

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

1.4 Free ASCII mode

(2) HEX to ASCII conversion (HTOA)

FUN 62

HTOA

HEX to ASCII conversion

Expression

Input —^ ^ ^TOA (n) B ]— Output

Function

When the input is ON, the hexadecimal data of

n

registers starting with

A

is

converted to the ASCII characters and stored in

B

and after.

The uppermost digit of source

A

is stored in lower byte of destination 6, and

followed in this order.

The allowable range of n is 1 to 32.

When index or constant value is set as source

A.,

this function can be

performed under the condition that n is equal to 1. If n is more than 1, a
boundary error is occured.

Execution condition

Input

Operation

Output

OFF

No execution

OFF

ON

Normal execution

ON

Operand

Device

Register

Con­

stant

Name

X

Y

S

L

R

Z

T.

c.

I

0

X

Y

s

L

R

w

T

c

D

F

I

0

I

J

K

Index

W W

w

W

W

w w

A

Source

V

V

V

V

V

V

V

V

V

V

V

V

V

V

V

V

n

Size

1 -32

B

Destination

V

V

V

V

V

V

V

V

V

V

V

Exampie

When R0010 is ON, 4 words data of RW100 to RW103 are converted into ASCII
characters, and stored in 8 words registers starting with D0220.

6F8C0926

45

Advertising