Chapt.2 Specifications

A/D Conversion

Digital Value

Digital Value

(a) 4-20mA range :D=15.625xA-62.5

(b) 1-5V range :D=62.5xA-62.5

(c) 0-10V range :D=25xA

D: Digital value

A: Analog value

Data Format

XW

F

E

D

C

B

A

9

8

7

6

5

4

3

2

1

0

B

*

*

*

*

*

*

*

D

D

D

D

D

D

D

D

D: Data bit (8bits)

0-250 (HOO - HFA)

(Over-voltage/over-current input 255 counts)

B: External line abnormal detection bit

0= Normal

1=Abnormal'

: Always 0

When all data bits are 0 •• Current input line open

When all data bits are 1 •• External power is OFF

4 words occupied

(X4W)

r

XWn

CH1

XWn+1

CH2

XWn+2

CH3

XWn+3

CH4

NOTE

1. In the voltage input specification, the data bits do not become 0 when there is an open circuit

between the input terminals. (They become indeterminate between 0 and 250.)

2. It is recommended that unused channels are shorted between the input terminals.