1.2 S2T CPU Module

1.2.2

Status display LEDs

These LEDs show operation states of the S2T.

Status display LEDs

Name

Display

States

Remark

RUN (Green)

Lit

Operating state (RUN Mode)

Blink

HOLD Mode

Out

Stopped state (HALT Mode) or Error Mode

FLT (Red)

Lit

CPU abnormal or I/O abnormal

Blink

CPU abnormal

Out

Normal

BAT (Green)

Lit

Battery normal

Blink

Battery caution

Out

Battery abnormal or no battery

1.2.3

Operation Mode Switch

The Operation Mode Switch is provided on the CPU module.

This switch controls S2T operation (RUN/HALT).

HALT-----------------Stop user program execution (HALT mode)

A

U

RUN

-Start user program execution (RUN mode)

CPU status is shown below after power up or after the operation mode is changed to
RUN from H ALT mode.

Setting

Position

Initial Load Program

exe: executed

-: not executed

Operation

mode

Operation Mode

Change by the

Programming tool

HALT

SW-1=OFF

exe

HALT

Not available

SW-1=ON

-

RUN

SW-1=OFF

exe

RUN

available

SW-1=ON

-

As shown the above table, initial load (user program transfer from Flash ROM to

RAM) performs when setting SW-1 to OFF.

NOTE

i.

The operation mode switch is set to HALT at the factory.

ii. Normally the programming is activated in the HALT mode,

ill. For details of the operation mode, see "S2T user's manual".

iv. The RAM is back-up by both internal capacitor and built-in battery of the S2T. When they go

down and the S2T can't keep retentive area in the RAM, CPU checks user program BCC.

CPU registers error if error is occurred.