Chapt.3 Precautions for I/O Modules

3.4 Precautions for AC Output Modules

(

1

)

(

2

)

Over-Current Protection Coordination
One 2A fuse per 4 output points is mounted in the triac output module.

Although, taking account of protecting elements by the fuse blowing even

in load short circuits, when the fuse blows the semiconductors are
subjected to considerable damage. Therefore, take care in handling and

wiring so that short circuits will not occur.

If an inductive load is connected, transient overvoltage will be generated at

the output is changed to OFF. To prevent malfunction caused by this surge
voltage, a CR snubber circuit is installed in the AC output module.

Flowever, to prevent the problem for other signal systems, install a surge

absorption element in parallel with the inductive load (install a surge
absorption element as near as possible to the inductive load).

Surge absorption element:

' Varistor (for the voltage clamp)

''-j

Bi-directional overvoltage absorption element with

a rated voltage of approx. 1.2 times of the max.

voltage (peak voltage)

Snubber (CR) circuit (for high-frequency attenuation)

R(£5) =

C(pF)

H hCIM

DC resistance value of the load

Jf____ ¡1 (I: peak value of load

10

20 current in ordinary time)

(3)

Because the AC output module does not have a zero-cross function, the

OFF^ON occurs regardless of the load voltage phases. Flowever, the
ON-OFF change occurs when load current is near zero. Check this point
in load response.