3 maintenance parts – Toshiba SX 2000 User Manual

Page 164

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

5.3 Maintenance parts

5.3 Maintenance parts

To recover from failure quickly, it is recommended to keep the following spare parts:

Part

Quantity

Remarks

I/O modules

One of each

type used

For the relay contact output, the contact life must be

taken into account. See Section 2.3.

Fuses

Number to be

used

See Section 5.5.

Battery modules

1

For emergency use. See Section 5.4. (GBT611*AS)

CPU modules

1

Keep a minimum of 1 each to reduce down-time to

the minimum.

Power supply modules

1

Programming tool

1set

Useful for detecting the cause of a failure.

Master program

As required

Keep on MO or the like.

Do not touch activated terminals of I/O modules and bases. Keep the terminal covers closed

during power ON.

This can cause electrical shock or injury.

NOTE

Store batteries in a cool (25°C or less) place as self-descharge is greater at high temperatures.

6F8C0926

147