Chapt.1 System Configuration

1.8 Network Modules

By applying the following 6 types of network module according to the system
requirements, the S2T can configure the flexible and efficient control systems.

• TOSLINE-F10

The Controller to Controller data linkage and remote I/O systems are configured

by the TOSLINE-F10 data transmission equipment.

Up to 8 modules model 2000 stations can be mounted on any slots, in the same

way as I/O modu

es.

UN611/UN612

(High-speed setting)

UN611/UN612

(Long-distance setting)

Cable

twisted -pair cable

Topology

Bus

Transmission speed

750kbps

250kbps

Transmission
distance

500m

1km

No. of stations

Max. 32 stations

Transmission
capacity

32 words

Response speed

7ms (when 32 words)

12ms (when 32 words)

TOSLINE-S20/S20LP

The TOSLINE-S20 is a Local Area Network (LAN) for a factory automation systems. It
can achieve high-speed data linkage between the Controllers and communication

between industrial computers.

Up to 2 modules model 2000 stations can be mounted on station module slots.

SN625

SN626

Cable

Co-axial cable

Optical fiber cable

Topology

Bus

Transmission speed

2Mbps

Transmission
distance

1km

10km

( 1 km between stations )

No. of stations

Max. 64 stations

Trarsmission
capacity

1024 words WO - W1023/W1024 - W2047

Response speed

Min. 5ms in scan transmission

The TOSLINE-S20LP is a double-loop system using optical fibers and can continue
data linkage if any problem is occured in one loop.
Transmission data capacity is expanded to 4k words.

SN627

Cable

Optical fibe cable

Topology

Double-Loop

Transmission speed

2Mbps

Transmission

Distance

between stations

1 km (4km using the optical repeater)

total

30km

Number of stations

Max. 64 stations/loop

Transmission capacity

4,096words

W0000-W2047 (Z/W) and any 2048word

registers (using XFER instruction)

Response speed

Min. 5ms in scan transmission

62

Sequence Controller S2T