4.7 I/O wiring

4.7 I/O wiring

Pay attention to the following points when mounting and wiring the I/O modules.

Basic unit

Low-power

signal duct

Q.

Q.

3

yj
O'

5

o

Q.

c

I I I I

II II

p

u

Low-power

High-power

T

i

system I/O

I I I I

system I/O

I I

J J J

J J ILILT

Expansion unit

T

—I—I—I—I—

—I—I—I—I—

I

Q.

Q.

3

yj
O'

5

o

Q.

I I I I

Low-power

I I I I

High-power

system I/O

I I I I

system I/O

I I I I

J J J

J J L LILT

70mm or more

200mm or more

◄------------------------------►

High-power

signal duct

Power line

Low-power system I/O

High-power system I/O

DC input module

AC input module

Analog input module

DC output module

Analog output module

AC output module

Pulse input module

Positioning control module

Serial Interface

Transmission module

Relay output module

B

(1)

To improve the unit’s resistance to signal interference, install modules for low-

voltage signals toward the left of the unit, and modules for power signals toward
the right. Also, separate the wires of each.

(2)

Allow at least 70mm clearance between the units and between other control

equipment to allow access for maintenance and ventilation.

(3)

When installing the unit near high-voltage or high-power equipment, leave at

least 200mm clearance, or shield the unit with a steel plate.

(4) Refer to the following table for the size of I/O cables.

Type of module

Cable size

16-point module

0.5~1.25mm^

32/64-point module

0.1~0.3mm2

However, for common lines, use a thicker size which takes account of the

current capacity. Also, for cables outside the panel, the use of cable of at least

1.25mm^ is recommended to keep the impedance low.