5 modesetting, Mode setting, One to n configuration : 4-wire system – Toshiba SX 2000 User Manual

Page 49

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

One to N configuration : 4-wire system

Chapt.1 System Configuration

S2T

Shielded twisted-pair cable

Serial ASCII device

220n

On the S2T, removable terminal block is provided for cable connection.

Connect termination resistor 1/2 W - 220

Q.

between RXA and RXB, and between

TXA and TXB at the both terminal stations.

1.4.5

Modesetting

The operation mode of the S2T’s link port is selected by the special resister provided
on the S2T CPU module.

The operation mode is internally set at the timing of power-up. Setting changes while

power on is not effective.

To select the computer link mode, the special resister SW069 set to " 2 " . (SW069=2)

At the factory, the computer link mode is selected.

S2T

resister

Name

Function

SW069

link port operation mode

0: computer link mode

2: Free ASCII mode

32

Sequence Controller S2T

Advertising