Chapt.5 Maintenance and

Checking

5

5.1 Daily checking items

To maintain the system and to prevent troubles, check the following points on daily

basis.

Item

Content of checking

Corrective measures

LEDs on the

power supply and

S2T CPU modules

POWER(green):Lit when 5V power normal

If the LEDs are abnormal,

see Section 6, Trouble­

shooting.

RUN(green) :Lit when operating normally

FLT(red) :Not lit when the CPU normal

BAT (green) : Lit when the battery voltage

normal

Input LEDs

(digital input)

Lit when the corresponding input signal is ON.

Check that the input

voltage

is

within

the

specified range.

• Check that the input tem-

inal block is not loose.

Check that the modules

are installed securely.

Output LEDs

(digital output)

Lit when the output is ON and the correspond­

ing external load should operate.

Check that the external

load voltage is within

the specified range.

• Check the built-in fuses.

Check that the output

terminal

block

is

not

loose.

Check that the modules

are installed securely.

Switches on the

CPU mobule

Operation

is

executed

when

the

operation

mode switch (HALT/RUN) is to RUN.

• Change the switch to

the correct position.

A CAUTION

1. Perform daily checks, periodical checks and cleaning to maintain the system in normal

condition and to prevent unnecessary troubles.

2. Turn off power immediately if the S2T or related equipment is emitting smoke or odor.

Operation under such situation can cause fire or electrical shock. Also unauthorized

repairing will cause fire or serious accidents. Do not attempt to repair. Contact Toshiba for

repairing.