R0662s – Toshiba SX 2000 User Manual

Page 93

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

Chapt.2 Specifications

R0S62S

R0662S

Item

No. of output point

Load Voltage

Maximum Load

Minimum Load

Delay

time

ON Delay

OFF Delay

Leakage current when OFF

External connections

Common

configuration

No. of commons

No. of output points

per common

Common polarity

Current consumption

Withstand voltage

External Relay Coil Power

Required

ON/OFF life of relays

Weight

R0662S

8 points (each point isolated)

110Vdc, +10%(Max.) /240Vac, +10%(Max.)

2A/point (resistive load) and 1A/point (inductive load) at

240Vac/24Vdc

0.5A/point (resistive load) and 0.1A/point (inductive load) at

110Vdc

50mW (5Vdc or more)

10ms or less

15ms or less

0mA or less

18-point terminal block

1

1 point

No polarity

40mA (5Vdc) or less

1500Vac /1 minute

24Vdc+10%-100mA/all points ON (10mA/ point)

Electrical: See the figures of life curves of the output relay,

Mechanical: 20milion times

Approx. 250g

Circuit Configuration

Terminal Connections

No over load protection fuses

are built into this module.
Therefore connect fuses
externally suitable to the
current capacity.

76

Sequence Controller S2T

Advertising