1.4 Free ASCII mode

CPU register o S2T link port

<Receiving>

Operation:

When the instruction input is ON, one set of message (from start character to
the trailing code) which is received by the link port is read from the receive

buffer, and stored in the CPU registers. The transfer size is fixed to 256

words. The execution status and the message length (in bytes) are stored in
the status flag.
The instruction input must be kept ON until the receiving operation is
complete.

Example:

Source designation

Transfer size

Destination designation

DOOOO

D0001

HOO

H30

D0002

00256 (fixed)

D0005

HOO

H04 1

00000

D0003

Execution status

D0006

00100 1

D0004

Message length

Link port

D0100 (CPU register)

When ROOOO is ON, one set of received message is read and stored in

D0100 and after.

Execution status:

HOOOO .

H0001 .
H0002 .
H0003 .
H0004 .

.. Normal complete
.. Communication error (parity error, framing error)
.. Message length over (more than 512 bytes)
.. Receive buffer over flow
.. Receive timeout (from start character to the trailing code)

Baudrate

Time-out setting

300, 600, 1200 bps

30 seconds

2400 bps

15 seconds

4800 bps

7 seconds

9600 bps

3 seconds

19200 bps

1.5 seconds

Message length:

0......................... No receive message

1 to 512 ... Message length in bytes

Remarks:

The instruction error flag (S0051) comes ON in the following cases, (no
operation)

• The leading address for the link port designation is other than 0.

• Transfer size is other than 256.

• Mode setting of the link port is not the free ASCII mode.

• This instruction is programmed in the sub-program #1.