1.4 Free ASCII mode

1.4.4

RS-485 cable connection

Cable connection examples show as below.

• Use shielded twisted-pair cable for data communication suited to RS-485

standard. The cable shield should be connected to single -point ground.

One to one configuration : 4-wire system

S2T

Shielded twisted-pair cable

1 km max.

Serial ASCII device

TXA

____ A...................... ....................................... A_____

RXA

1 XX

TXB

RXB

RXA

TXA

>

ZD0(

TERM

RXB

TXB

SG

SG

1 ............................................................................................... 1/

R: 1/2 W-120 £2

• S2T, removable terminal block is provided for cable connection.

• Short between RXA and TERM for termination at the S2T.

• Connect termination resistor 1/2 W - 120 Q between RXA and RXB at the serial

ASCII device.

One to one configuration : 2-wire system

S2T

Shielded twisted-pair cable

Serial ASCII device

On the S2T, removable terminal block is provided for cable connection.

Short between RXA and TERM for termination at the S2T.

Connect termination resistor 1/2 W - 120 Q between RXA and RXB at the serial

ASCII device.