1.3 Computer link mode

Tablel-SSupplementary function for computer link

The following supplementary function are prepared for applying to various system
control using computer link function.

S2T

resister

Name

Function

SW038

Response delay mode on the

programmer port

(RS232C)

Setting value: 0-30

A response message is issued from the S2T after

(setting value *10) ms.

SW057

Response delay mode on the

LINK port (RS485)

Setting value: 0-30

A response message is issued from the S2T after

(setting value *10) ms.

1.3.2

System configuration

The following figure shows the system configuration using computer link function.

S2T, link port (RS-485), one-to-N configuration (N is max. 32) is available. If the
master computer has RS-232C interface only, the RS-232C/RS-485 converter (ADP-
6237B) can be used.

S2T, programmer port (RS-232C), one-to-one contiguration is available.

One-to-N configuration

(S2T: RS-485)

Master Computer

Max. 32

One-to-one configuration

(S2T : RS-232C)

Master Computer

S2T

RS-232C

(15 m max.)

6F8C0926