Chapt.3 Precautions for I/O Modules

(4)

If the AC lines are installed in parallel with high frequency or power lines,

induced current may cause erroneous input. In this case, take necessary

countermeasures as follows.

• Change the installation route of AC input lines so that they are not

parallel with power lines and high frequency lines.

• Use twisted-pair cables as input lines.

• Use shielded cables as input lines.

• Use relays at the leading in the control panel (the relay must satisfy

larger ON current).

• Install a bleeder resistor to lower the input impedance.

(5)

If the input module and an inductive load are connected in parallel, a surge

voltage generated at both-ends of the load when the contact is changed to

OFF may cause a malfunction of the S2T. In the case, install a surge
absorption element in parallel with the load to suppress the surge voltage.

Input module

Surge absorption element (snubber circuit, etc.)

1 1 6

Sequence Controller S2T