8 wiring of the computer link, One to one configuration – Toshiba SX 2000 User Manual

Page 158

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

4.8 Wiring of the computer link

4.8 Wiring of the computer link

Cable connection examples show as below.

• Below figure shows an example of cable connection using the RS-232C/RS-485

converter (ADP-6237B).

• Use shielded twisted-pair cable for data communication suited to RS-485

standard. The cable shield should be connected to single -point ground.

One to one configuration

Master

computer

TXD

RXD

RTS

CTS

SG

DTR

DSR

CD

RS-232C

(max. 15m)

RS-232C/RS-485 converter

(ADP-6237B)

3

RXD

TXA

2

TXD

TXB

5

CTS

RXA

4

RTS

RXB

7

SG

SG

6

DSR

TERM

20

DTR

FG

8

CD

1

FG

25-pin

connector

Terminal

block

---

S2T

30C

RXA

RXB

TXA

TXB

SG

TERM

RS-485

(max. 1km)

Terminal

block

On the S2T, removable terminal block is provided for cable connection.

Short between RXA and TERM for termination at both the S2T and the

ADP-6237B.

If the master has RS-485 (or RS-422) interface and the S2T is connected to the

master directly, connect termination resistor 1/2 W - 1 2 0 Q between RXA and RXB

at the master end.

B

6F8C0926

141