6�- CirLAMP Node 1 ��� 10V

6.1.- INSTALLATION OF THE UNIT

6�1�1� PRELIMINARY RECOMMENDATIONS

See section

“4�1�1� PRELIMINARY RECOMMENDATIONS”�

6�1�2� INSTALLATION

Terminals, opening covers or removing elements can expose parts that are

hazardous to the touch while the unit is powered. Do not use the unit until it is

fully installed.

The unit has two cable seal/gland terminals (

Figure 85

):

Input for the power supply cables.

Output towards the lamp and 1 to 10V output to control the ballasts.

The unit must be opened to complete the installation; to do this unscrew the four front screws.

Entrada alimentación

Input for power supply cables

Salida hacia la lámpara

Output towards the light

Tornillo

Screw

Figure 85:Position of the CirLAMP 1 to 10V cable seal terminals and screws

Connect the unit with 5 x 2.5 mm

2

hoses.

To pass the hoses through the cable seal terminals, which guarantees the IP65 protection de-

gree of the unit, you need to pierce the cable seal from outside of the box with a 3 mm

2

punch

(

Figure 86

)

78

CirLAMP system

Instruction Manual