9.3.- CirLAMP Node 1 ... 10 V

AC power supply

Mode

Self-powered

Rated voltage

184 ... 276 V ~

Frequency

50/60Hz

Consumption

2W 16VA

Installation category

CAT III 300 V

Voltage measurement circuit

Voltage measurement margin

184 ...276 V ~

Input impedance

600 MΩ

Installation category

CAT III 300 V

Current measurement circuit

Current measurement margin

0.1 ... 3A

Minimum measurement current (Istart)

0.08 A

Installation category

CAT III 300 V

Measurement accuracy

Voltage measurement

< 5% of full-scale

Current measurement

< 5% of full-scale

Active and reactive power measurement

< 5% of full-scale

Outputs 1 ��� 10V (In accordance with EN60929:2011)

Output voltage

1 ... 10V

Current

10

μ ... 2 mA

PLC (Power Line Communications)

Hardware

CENELEC B DCSK

Baud rate

2400 bauds with repeater management

Protocol

CirPLC (DCSK)

Insulation

Alternating voltage

4 kV RMS 50 Hz for 1 minute

Overimpulse

1.2/50 μs 0R source impedance

2 kV UNE-EN 61000-4-5:2007 + CORR:2010

Environmental features

Operating temperature

-25ºC... +70ºC

Storage temperature

-35ºC... +80ºC

Relative humidity (non-condensing)

5 ... 95%

Maximum altitude

2000 m

Protection degree

IP65

Mechanical features

Dimensions (mm)

Figure 101

Weight

250 gr

Enclosure

Polycarbonate