Communications hardware requirements, Rtu communication requirements, Tcp communication requirements – Basler Electric BE1-700 Modbus Protocol User Manual

Page 20: Detailed message query and response, Read holding registers, Query, Communications hardware requirements -10, Rtu communication requirements -10, Tcp communication requirements -10, Detailed message query and response -10

Advertising
background image

1-10

BE1-700 Modbus™ Protocol

9376700991 Rev D

Figure 1-14. DOS Command Example of Default IP Address Detected


7) Once your PC has an IP address, the BE1-700 BESTCOMS™ PC software program or the Digi

Discovery program (

dgdiscvr.exe) can be used to determine the IP address of the BE1-700. A BE1-

700 with style number xxxxx7x (Modbus/TCP over Ethernet) must use the Modbus ping software

program (

ruiping.exe)

8) In the Basler Modbus/TCP Device Discovery program, click on Refresh to discover the IP address.

Communications Hardware Requirements

RTU Communication Requirements

The BE1-700 RS-485 physical interface is three positions of a terminal strip with locations for

Send/Receive A (A), Send/Receive B (B) and Signal Ground (C). Refer to the BE1-700 Instruction Manual

(9376700990) for further details.

TCP Communication Requirements

The BE1-700 Ethernet port (RJ-45) is used with the Ethernet option. The relay supports 10BaseT using

Cat 5 / Cat 5e shielded twisted pair. Refer to the BE1-700 Instruction Manual (9376700990) for further

details.

Detailed Message Query and Response

A detailed description of BE1-700 supported message queries and responses is provided in the following

paragraphs.

Read Holding Registers

This query message requests a register or block of registers to be read. The data block contains the

starting register address and the quantity of registers to be read. A register address of N will read holding

register N+1. If the query is a broadcast (device address = 0), no response message is returned.

Query

Device Address

Function Code =

03 (hex)

Starting Address Hi

Starting Address Lo

No. of Registers Hi

No. of Registers Lo

CRC Hi error check

CRC Lo error check
The number of registers cannot exceed 125 without causing an error response with the exception code

for an illegal function.