3-22

BE1-700 Modbus™ Protocol

9376700991 Rev D

47374

Current Group Control Setting

ASC(1)

Read only: ASCII character 0, 1, L

47375

Current Output Control Settings (OutputPulse0) MSBs

BM(16)

Read only:

Bits 15 to 7 - Spare

Bit 6 - Output 6 pulse low

Bit 5 - Output 5 pulse low

Bit 4 - Output 4 pulse low

Bit 3 - Output 3 pulse low

Bit 2 - Output 2 pulse low

Bit 1 - Output 1 pulse low

Bit 0 - Output A pulse low

47376

Current Output Control Settings (OutputPulse1) LSBs

BM(16)

Read only:

Bits 15 to 7 - Spare

Bit 6 - Output 6 pulse high

Bit 5 - Output 5 pulse high

Bit 4 - Output 4 pulse high

Bit 3 - Output 3 pulse high

Bit 2 - Output 2 pulse high

Bit 1 - Output 1 pulse high

Bit 0 - Output A pulse high

47377

Current Output Control Settings (OutputLatch0) MSBs

BM(16)

Read only:

Bits 15 to 7 - Spare

Bit 6 - Output 6 latch low

Bit 5 - Output 5 latch low

Bit 4 - Output 4 latch low

Bit 3 - Output 3 latch low

Bit 2 - Output 2 latch low

Bit 1 - Output 1 latch low

Bit 0 - Output A latch low

47378

Current Output Control Settings (OutputLatch1) LSBs

BM(16)

Read only:

Bits 15 to 7 - Spare

Bit 6 - Output 6 latch high

Bit 5 - Output 5 latch high

Bit 4 - Output 4 latch high

Bit 3 - Output 3 latch high

Bit 2 - Output 2 latch high

Bit 1 - Output 1 latch high

Bit 0 - Output A latch high

47379

Current Output Contact Status

BM(16)

Read only:

Bits 15 to 7 - Spare

Bit 6 - Output 6

Bit 5 - Output 5

Bit 4 - Output 4

Bit 3 - Output 3

Bit 2 - Output 2

Bit 1 - Output 1

Bit 0 - Output A

47380

Active Alarm Flags (Sum Flags) MSBs

BM(16)

Read only: Bits 15 to 0 - Spare