Introduction

This section details the register formats and data ranges of the previous section. The two sections

combined provide all information necessary to communicate with the BE1-700 Modbus™ Holding

Registers.
Any Holding Register not listed in the Register Table is an unassigned Holding Register. A value of zero

always results when reading an unassigned Holding Register. Writes to unassigned Holding Registers are

legal but no action will be taken (that is, the write is ignored).

Logic Settings

Logic settings consist of a combination of modes, masks, terms, and term counts. Logic modes are

specific to each logic set, while the masks, terms, and term counts have value definitions consistent

throughout all logic sets. A single logic equation consists of a "mask" and "term" pair. The logic "term

count" is used only in VOA, VO1-VO15 virtual output logic blocks.
The logic "mode" enables or disables the logic equation for that logic block.
The logic "mask" corresponds to the System Status bits to be evaluated. These bits are referenced in the

desired logic equation and are set to 1 (non-used bits masked out as 0's).
The logic "term" corresponds to the System Status bit's TRUE or FALSE state, referenced in the desired

logic equation where only the TRUE bits in the equation are set to 1.
he logic "term count" may be of one of four logic types which are NONE (logic disabled), OR only ( a + b +

c), AND only (a * b * c) or MIXED (a * b + b * c).
The following defines all logic set parameters.

Logic Modes


41505

Programmable 50TP Logic Mode

INT

41539

Programmable 50TQ Logic Mode

INT

41556

Programmable 150TP Logic Mode

INT

41590

Programmable 150TQ Logic Mode

INT

Read and Write:

0 for disabled

1 for enabled

41522

Programmable 50TN Logic Mode

INT

41573

Programmable 150TN Logic Mode

INT

Read and Write:

0 for disabled

1 for calculated neutral

2 for measured ground

41658

Programmable Breaker Fail Logic Mode

INT

Read and Write:

0 for disabled

1 for enabled

41691

Programmable 51P Logic Mode

INT

41725

Programmable 51Q Logic Mode

INT

41708

Programmable 51N Logic Mode

INT

41759

Programmable 151N Logic Mode

INT

Read and Write:

0 for disabled

1 for calculated neutral

2 for measured ground