Global setting parameters, Serial port setting parameters, Global setting parameters -13 – Basler Electric BE1-700 Modbus Protocol User Manual

Page 61: Serial port setting parameters -13

Advertising
background image

9376700991 Rev D

BE1-700 Modbus™ Protocol

3-13

Global Setting Parameters

40602-03

Power System Nominal Voltage

FP

Read and Write: 50 to 250

40604-05

Power System Nominal Current

FP

Read and Write: 0.5 to 10.0

40606-07

Breaker Fail Time Delay

LI

Read and Write: 50 to 999 milliseconds, 0 to disable

40608-09

Programmable 51 Curve Constant A Delay

FP

Read and Write: 0.0000 to 600.0000

40610-11

Programmable 51 Curve Constant B Delay

FP

Read and Write: 0.0000 to 25.0000

40612-13

Programmable 51 Curve Constant C Delay

FP

Read and Write: 0.0000 to 1.0000

40614-15

Programmable 51 Curve Constant N Delay

FP

Read and Write: 0.5000 to 2.5000

40616-17

Programmable 51 Curve Constant R Delay

FP

Read and Write: 0.0000 to 30.0000

40618

Input 1 Contact Recognition Time Delay

SI

40619

Input 1 Contact Debounce Time Delay

SI

40620

Input 2 Contact Recognition Time Delay

SI

40621

Input 2 Contact Debounce Time Delay

SI

40622

Input 3 Contact Recognition Time Delay

SI

40623

Input 3 Contact Debounce Time Delay

SI

40624

Input 4 Contact Recognition Time Delay

SI

40625

Input 4 Contact Debounce Time Delay

SI

Read and Write: 4 to 255 milliseconds

40746-870

Contiguous Poll Block Assignments

INT

Read and Write:

0 if Unassigned

1 to 9874: Holding Register 40001 to 49874

40871

Setting Group Control On Time

INT

Read and Write: 0 to 10 seconds

40872

Setting Group 1 Automatic Control Switch Time

SI

40874

Setting Group 1 Automatic Control Return Time

SI

Read and Write: 0 to 60 minutes

40873

Setting Group 1 Automatic Control Switch Level

SI

40875

Setting Group 1 Automatic Control Return Level

SI

Read and Write: 0 to 150%

40876

Setting Group 1 Tracking Element

INT

Read and Write: 0 to 8 (0 = 51P, 1 = 51Q, 2 = 51N, 3 = 151N, 4 = 791, 5 = 792, 6 = 793, 7 = 794,

8 =60FL)

40903-04

60FL Loss of Current Auto Block Setting

ASC(3)

Read and Write: ENA/DIS

40905-06

60FL Loss of Voltage Auto Block Setting

ASC(3)

Read and Write: DIS/ PNQ/ PN/ PQ/ NQ/ P/ N/ Q

Serial Port Setting Parameters

40962

Serial Port 0 Baud Rate

INT

40980

Serial Port 2 Baud Rate

INT

Read and Write:

0 - 300 baud (Do not select for Port 2 Modbus communications)

1 - 600 Baud (Do not select for Port 2 Modbus communications)