Basler Electric BE1-700 Modbus Protocol User Manual

Page 75

Advertising
background image

9376700991 Rev D

BE1-700 Modbus™ Protocol

3-27

47472

Peak Demand Since Reset Timestamp - day

INT

47477

Peak Demand Since Reset Timestamp - day

INT

47482

Peak Demand Since Reset Timestamp - day

INT

Read only: Any value (days since 01/01/1984)

47463-64

Peak Demand Since Reset Timestamp - millisecond

LI

47468-69

Peak Demand Since Reset Timestamp - millisecond

LI

47473-74

Peak Demand Since Reset Timestamp - millisecond

LI

47478-79

Peak Demand Since Reset Timestamp - millisecond

LI

47483-84

Peak Demand Since Reset Timestamp - millisecond

LI

Read only: 0 to 86,399,999 milliseconds

47486

Reset Logic Alarm Information

SI

47487

Reset Major Alarm Information

SI

47488

Reset Minor Alarm Information

SI

47489

Reset Relay Alarm Information

SI

47491

Clear Fault Log

SI

47492

Trigger Fault Record

SI

47493

Clear Events Report

SI

Read: 0

Write: Any value will perform reset / trigger / clear.

47512

Fault Indicator

SI

Read only: Most recent Fault number (1 - 255)

47513

Fault Template Status

SI

Read only:

0: Template not valid for current Fault Selection (Refer to Register 40038). All FLT

template values will read 0.

1 to 255: Valid user selected Fault Number.


The following is the Fault Template (RPT):
47514

Fault Date and Time – day

INT

Read only: Any value (days since 01/01/1984).

47515-16

Fault Date and Time – milliseconds

LI

Read only: 0 to 86,399,999 milliseconds

47517

Fault Event Type

BM(16)

Read only:

Bit 0 for Breaker Fail

Bit 1 for Trip

Bit 2 for Logic

Bit 3 for Pickup

Bit 4 for Fault Record Trigger (Refer to Register 47492)

47518

Fault Active Group

SI

Read only: 0 to 1

47519

Fault Targets MSBs

BM(16)

Read only:

Bit 15 - Spare

Bit 14 - Spare

Bit 13 - Spare

Bit 12 - 51C

Bit 11 - 51B

Bit 10 - 51A

Bit 9 - 150TQ

Bit 8 - 50TQ

Bit 7 - 150TN