System data setting parameters, System data setting parameters -14 – Basler Electric BE1-700 Modbus Protocol User Manual

Page 62

Advertising
background image

3-14

BE1-700 Modbus™ Protocol

9376700991 Rev D

2 - 1200 Baud (Do not select for Port 2 Modbus communications)

3 - 2400 Baud

4 - 4800 Baud

5 - 9600 Baud

6 - 19K Baud

40981

Serial Port 2 Relay Address

INT

Read and Write: 0 to 65,534

40964

Serial Port 0 Software Flow Control

SI

Read: 0 if XON / XOFF Control is disabled, 1 if XON / XOFF Control is enabled

Write: 0 to disable XON / XOFF Control, 1 to 255 to enable XON / XOFF Control

40965

Serial Port 0 Page Length

SI

Read and Write: 0 for disabled, 1 to 40 for number of lines / page

40966

Serial Port 0 Acknowledgement Format

SI

Read: 0 if No acknowledge, 1 if Acknowledge enabled

Write: 0 for No acknowledge, 1 to 255 to enable acknowledge

40986

Serial Port 2 Modbus Parity

SI

Read and Write: 0 for No parity, 1 for Even parity, 2 for Odd parity

40987

Serial Port 2 Modbus Remote Delay

SI

Read and Write: 1 to 20: 10 to 200 milliseconds

40988

Serial Port 2 Modbus Stop Bits

SI

Read and Write: 1 for One stop bit, 2 for Two stop bits

40989

Password Security

SI

Read and Write: Default value is disabled, 1 to enable Password Security.

When Password Security is enabled, relay parameters can be changed via Modbus only

if access is obtained via the Access Password and Access Request holding registers and

released via the Exit register with value 89 (ASCII character 'Y').

0 to disable Password Security.

When Password Security is disabled, no access is required (Access Password, Access

Request, and Exit holding registers have no effect) and no password protection is used.

Global Parameters, holding registers 40080 - 40099 (ASCII command GS-PW) have no

effect on the Modbus serial port, COM2.

System Data Setting Parameters

41018

System Frequency

SI

Read and Write: 50 for 50 hertz, 60 for 60 hertz

41019-20

Phase Rotation

ASC(3)

Read and Write: ABC for ABC rotation, ACB for ACB rotation

41021

Phase CT Ratio

INT

41022

Ground CT Ratio

INT

Read and Write: 1 to 50,000

41033-34

Phase VT Ratio

FP

41041-42

Auxiliary VT Ratio

FP

Read and Write: 1.00 to 10000

41035-36

27/59 Voltage Sensing Mode

ASC(3)

41037-38

51/27R Voltage Sensing Mode

ASC(3)

Read and Write: PP for Line, PN for Phase