Global parameters, Global parameters -6, Table 3-1. report – Basler Electric BE1-700 Modbus Protocol User Manual

Page 54

Advertising
background image

3-6

BE1-700 Modbus™ Protocol

9376700991 Rev D

40039

Report Selection

SI

Read: Returns the current value of Report Selection.

Writing to Report Selection terminates previous report and initializes new report. See the

table for values.

40040

Report Focus

INT

Read: Returns the current value of Report Focus.

Write: See Table 3-1 for values.

Note: If an illegal Report Focus value is written, the user is not notified until a read of the

Report Text is attempted.

Note: Write to Report Selection and Report Focus to specify the report which will be

made available via the Report (RPT) Template. The template is the Report Text Block at

47595-719.

Table 3-1. Report

Report Text

47595-719

Report Selection

40039

Report Focus

40040

RA-LGC Report

0

Not used

RA-MAJ Report

1

Not used

RA-MIN Report

2

Not used

RA-REL Report

3

Not used

RF Report

4

Not used

RF-# Report

5

Value of # (1 – 255)

RF-NEW Report

6

Not used

RS Report

7

Not used

RS-# Report

8

Value of # (1 - 255)

RS-NEW Report

9

Not used

RS-F# Report

10

Value of # (1 – 255)

RS-ALM

11

Not used

RS-IO

12

Not used

RS-LGC

13

Not used

Global Parameters

Global Parameter registers 40080 - 40099 are effective only for serial communication ports active with

ASCII protocol and for the Modbus serial port, COM2, when Password Security register 40989 is enabled.

40080-83

Global Password

ASC(8)

40085-88

Setting Password

ASC(8)

40090-93

Control Password

ASC(8)

40095-98

Report Password

ASC(8)

Read: If global access granted, password ASCII strings are read. Otherwise, the ASCII string of

'*' characters is read.

Write: Password in ASCII string.

Note: If password written is less than 8 characters long, a binary zero value must be

included following the final password character.

40084

Global Path

BM(8)

40089

Setting Path

BM(8)

40094

Control Path

BM(8)

40099

Report Path

BM(8)

Read: Path associated with password

Write: Path associated with password

Bit 2 is set for COM 2 access.

Bit 1 is set for COM1 access.

Bit 0 is set for COM0 / FP access.