Basler Electric BE1-700 Modbus Protocol User Manual

Page 64

Advertising
background image

3-16

BE1-700 Modbus™ Protocol

9376700991 Rev D

41265-66

Major Alarm Mask MSBs

BM(16)

41267-68

Minor Alarm Mask MSBs

BM(16)

41269-70

Logic Alarm Mask MSBs

BM(16)

Read and Write:

Bit 15 - Spare

Bit 14 - Volts per Hertz alarm

Bit 13 - 60 Fuse Loss alarm

Bit 12 - Changes Lost alarm

Bit 11 - Freq Range alarm

Bit 10 - Spare

Bit 9 - Spare

Bit 8 - Logic = None alarm

Bit 7 - Flt Rpt Timeout alarm

Bit 6 - Virtual Output 15 alarm

Bit 5 - Virtual Output 14 alarm

Bit 4 - Virtual Output 13 alarm

Bit 3 - Setting Group Change Active alarm

Bit 2 - Loss of IRIG-B sync or IRIG-B decode problem

Bit 1 - An override is active in one or more outputs

Bit 0 - EEPROM Non fatal error

41266

Major Alarm Mask LSBs

BM(16)

41268

Minor Alarm Mask LSBs

BM(16)

41270

Logic Alarm Mask LSBs

BM(16)

Read and Write:

Bit 15 - User settings changed ('EXIT' with 'Y')

Bit 14 - Power reset alarm, hard reset of MPU

Bit 13 - Clock problem, real time clock has not been set

Bit 12 - Communicating failure alarm, read error on serial port

Bit 11 - Operating System Overload detected alarm

Bit 10 - Setting group override in effect

Bit 9 - Q demand alarm, excessive negative-sequence unbalance

Bit 8 - Neutral demand alarm

Bit 7 - Phase demand alarm

Bit 6 - Breaker alarm #3

Bit 5 - Breaker alarm #2

Bit 4 - Breaker alarm #1

Bit 3 - Recloser Lockout

Bit 2 - Recloser Fail

Bit 1 - Breaker fail alarm

Bit 0 - Out 1 CKT Open alarm

41272

Clock Format - Date

ASC(1)

Read and Write: M for mm/dd/yy format, D for dd/mm/yy format

41273

Clock Format - Time

SI

Read and Write: 12 for 12 hour clock, 24 for 24 hour clock

41274

Clock Format - Daylight Savings

SI

Read and Write: 0 for disabling Daylight Savings, 1 for enabling Daylight Savings

41275

Phase Demand Interval

SI

41276

Neutral Demand Interval

SI

41277

Negative-Sequence Demand Interval

SI

Read and Write: 1 to 60 minutes, 0 to disable

41281

LCD Backlight Timer

INT

Read and Write: 1 to 600 seconds, 0 for “always on”

Advertising